High Mast Lighting Tower For Large Area With LED Flood Lighting System
814133,MAIN ROAD GODDA
- Delivery
- 60 days
Specifications & requirements · 65
- Specification Name
- बड के िलए आवLयक अनुमत मूTय /Bid Requirement (Allowed Values)
- Height of High Mast Tower (in Meters)
- 16
- Installation and commissioning (Installation and commissioning work at multiple locations shall follow as per the guidelines of State/Central Govt rules and regulations as applicable)
- Yes. Including Civil work at site
- Onsite warranty (in Years)
- 2
- No of sections
- 2
- Effective length of each section (in m)
- 8.5
- Material construction: The mast shall be manufactured using special steel plates, conforming to
- 355 gradeasper BSEN10 025
- Bottom diameter (in mm) - Minimum
- 540
- Plate thickness for Middle (in mm) - Minimum
- 4
- Plate thickness for Bottom (in mm) - Minimum
- 5
- No of longitudinal welds/section (in Nos)
- 2
- Diameter of base plate (in mm) - Minimum
- 740
- Thickness of base plate (in mm) - Minimum
- 30
- Specification Name
- बड के िलए आवLयक अनुमत मूTय /Bid Requirement (Allowed Values)
- Maximum Wind load
- 50 m/sec
- Size of opening and closing door at base compartment of high mast (in mm) - Minimum
- 1200 x 250
- Ingress protection for Junction Box i.e. IP Class (as per IS/IEC:60529:2001 latest) Test Report from Central Government lab/NABL/ILAC accrediated lab and report shall furnish to buyer on demand
- IP 65
- No of core
- 3
- Cable category
- FR
- Size of cable (in Sq mm)
- 2.5
- Conductor material shall be
- Copper
- The winch shall have provision for manual operation in case of failure of the motor
- Yes
- The breaking load of each rope shall be at full load as per the relevant standard
- >/=2400 Kg
- No. of cores
- 3
- Cable shall be
- Unarmoured
- Conudctor material shall be
- Copper
- Cable Category
- C1
- Incoming power cable from feeder panel to base compartment of mast and cable shall conforming to
- IS:7098 (Part 1):1988 latest
- Feeder pillar panel for each mast
- Yes
- Feeder panel shall be suitable for
- 415 V, 3 phase, 4 wire, 50 Hz, AC
- The control panels shall be
- Stand mounted
- Ingress protection for feeder pillar panel i.e IP Class (as per IS/IEC:60529:2001 latest).Test Report shall furnish from Central Government lab/NABL/ILAC accrediated lab to buyer on demand
- IP 65
- Specification Name
- बड के िलए आवLयक अनुमत मूTय /Bid Requirement (Allowed Values)
- It shall be fabricated out of
- 14 SWG CRCA sheet steel
- Thickness of sheet (in mm)
- 2
- The panels shall be given pre-treatment and powder coated and color shall be
- Grey
- The stand shall be painted in
- Black color
- Cable entry shall be at the
- Bottom
- The panels shall have
- knock outs of the required cable
- Laminated circuit diagram shall be pasted
- inside of the door
- Feeder pillar shall have pad locking arrangement
- Yes
- Earth terminal
- 12 mm dia. Bolts
- Panel shall have a sloping cover to avoid accumulation of dust
- Yes
- Panel shall be provided with incoming & outgoing MCCB/MCB of appropriate rating and in desired quantity depending on total no of circuits in use
- yes
- Timer for automatic ON & OFF of lights with pilot lamps shall be provided
- Yes
- Bus bars material
- Yes. Copper
- No of Cores
- 1
- Size of cable (in Sq.mm)
- 4
- Cable Shall be
- Unarmoured
- The conductor material shall be
- Copper
- cable category
- C1
- No. of Luminaires for each high mast lighting tower (in Nos)
- 12
- LED Rating/System Wattage/Rated Power for each luminaire
- 200W
- Luminaire System Efficacy (Lumen/watt)
- >/= 100 Lm/Watt
- Specification Name
- बड के िलए आवLयक अनुमत मूTय /Bid Requirement (Allowed Values)
- Ingress Protection (IP Rating) as per IS:10322 (Part 1):1982 latest
- IP66
- Mounting brackets (included)
- Adjustable
- Input operating Voltage range and frequency
- 90 to 300 Volts AC at 50Hz+/-2Hz
- Rated voltage
- 230 V AC 50 Hz
- Colour temperature
- 6000K (+/- 500K)
- Optic lense material (UV stabilised) (Write NA for without optic lense supply)
- Poly carbonate lense
- Operating temperature range
- -20 deg C to +50 deg C
- The luminaire shall be protected against surges and transients( Internal)
- >/=5KV
- Number of electronic control gear per luminaire (power supplies)
- 2 Nos.
- Length of ISI marked three core wire (shall be provided along with supply of material)
- 50 cm