XLPE Cable For Working Voltage Up To And Including 1.1 KV Marked To IS 7098 (Part 1)
628007,Heavy Water Plant Tuticorin
- Delivery
- 60 days
Specifications & requirements · 25
- Bis Required
- Yes
- Specification Name
- बड के िलए आवNयक अनुमत मूTय /Bid Requirement (Allowed Values)
- Cables suitable for use in mines
- Yes, No
- Specification Name
- बड के िलए आवNयक अनुमत मूTय /Bid Requirement (Allowed Values)
- Classification of cables for improved fire performace category
- C2 - FR-LSH
- Nominal Area of Conductor (in Sq mm)
- 1.5
- Number of Cores
- 3
- Material of Conductor
- Plain Copper
- Construction of the conductor
- Stranded and shaped
- Colour of XLPE Insulation
- Red, Yellow, Blue, Black
- Type of Inner Sheath
- Thermoplastic
- Type of Cable
- Armoured cable
- Material of Armouring
- Galvanized round steel wire, Galvanized steel formed wire
- Type of Armouring
- Single wire
- Colour of Outer Sheath
- Black
- Manufacturer's Identification on Cable
- as per Cl.17.1 of IS:7098 Part 1: latest
- Cable Identification
- as per Cl.17.2 of IS:7098 Part 1: latest
- Type of Sequential Marking on Cable
- Screen printing on cable
- Packing and Marking
- as per Cl.18.1 and 18.2 of IS:7098 Part 1: latest
- Cable Wound on
- ISI Marked Wooden drum
- Drum Standard
- as per IS:10418 latest
- Test certificates
- FRLSH PROPERTIES ,OXIGEN INDEX ,TEMPRATURE INDEX ,CONDUCTER DC RESISTANCE ,INSULATION STRENGTH AND ELONGATION CERTIFICATE,IR AND HV TEST CERTIFICATE AS PER RELEVANT TEST STANDARD SHELL BE PERFORM AND SUBMITTED ALONG WITH SUPPLY OF MATERIAL.
- VOLTAGE GRADE OF INSULATION
- 1100V
- TYPE OF INSULATION
- ST2 AS PER IS5831
- APPLICABLE STANDARDS
- FRLS-ASTM D2863, CONDUCTOR-IS8130, ARMOUR-IS3975