Online UPS (?10 KVA) With Battery Conforming To IS 16242 (Part 1)
***********Kozhikode
GeM masks the full address in this document.- Delivery
- 60 days
Specifications & requirements · 19
- Bis Required
- Yes
- Specification Name
- बड के िलए आवPयक अनुमत मूWय /Bid Requirement (Allowed Values)
- Rating (in KVA)
- 3
- Input Voltage (AC, 50 Hz)
- Single Phase, 160V - 260V
- Output Voltage (AC, 50 Hz)
- Single Phase, 230V±1%,
- Availability of Inbuilt Isolation Transformer
- No
- Minimum Overload Capacity of Online UPS
- 120% of Rating in KVA for 10 minutes
- Type of Battery
- SMF-VRLA (Sealed Maintenance Free-Valve Regulated Lead Acid) / Stationary Lead Acid Batteries
- Backup Time
- 30.0 (minute)
- Type of Mounting of Online UPS
- Floor Standing
- Specification Name
- बड के िलए आवPयक अनुमत मूWय /Bid Requirement (Allowed Values)
- Ingress Protection
- IP21 Or higher
- Operating Temperature Range (Lower Limit)
- - 5°C to 0°C, 5°C to 10°C
- Operating Temperature Range (Upper Limit)
- 45°C to 50°C
- Battery Bank
- SUPS shall be supplied with 72V Battery bank (06x12V SMF-VRLA Batteries)
- Battery Capacity
- Minimum 42Ah battery capacity
- Battery Rack
- Heavy duty powder coated MS battery rack with all mounting hardware
- Battery Accessories
- Battery Interconnecting cables, copper lugs, battery fuse/MCB and all accessories shall be supplied.
- Installation
- Supply, installation testing and commissioning at site including connection to existing PDU and 02 Stub Servers.